Clearwater E6 Air Blower Replacement

Clearwater E6 air blower replacement — We recently attended a callout to a Clearwater E6 sewage treatment plant after the existing air blower failed, preventing the plant from receiving the aeration required for biological treatment.

The air blower is one of the most important components within an aerated sewage treatment plant. Without a constant supply of oxygen, the biological treatment process begins to deteriorate, reducing treatment efficiency and affecting final effluent quality.

Air Blower Failure

Following our inspection, the original air blower was confirmed to have failed and required replacement.

The failed unit was removed before a new JDK 60 air blower was supplied, installed and commissioned.

  • Failed air blower removed
  • New JDK 60 air blower installed
  • New blower commissioned
  • Air delivery restored
  • Aeration process returned to normal operation
Failed air blower and new JDK 60 replacement on Clearwater E6 treatment plant
The failed air blower before replacement and the new JDK 60 air blower after installation.

Electrical and Operational Testing

Once the new blower had been installed, a full electrical inspection and operational check of the treatment plant was completed.

  • Electrical components tested
  • Control panel inspected
  • Plant controls checked
  • Air delivery confirmed
  • Aeration distribution checked
  • Complete plant operation tested

Following commissioning, the treatment plant was found to be operating correctly with no further operational faults identified.

Clearwater E6 sewage treatment plant following JDK 60 blower replacement
The Clearwater E6 sewage treatment plant operating correctly following installation of the new air blower.

Aeration Restored

After installation of the new JDK 60 blower, air delivery was restored throughout the treatment plant.

The aeration process was found to be operating normally, with satisfactory air distribution and no further faults identified during testing.

Sludge and Crust Inspection

As part of the visit, sludge and crust levels were measured within the primary and final settlement chambers.

  • Primary crust: 50mm
  • Primary sludge: 200mm
  • Final crust: 50mm
  • Final sludge: 150mm

All readings remained within acceptable operating limits, meaning desludging was not required at the time of the visit.

Plant Returned to Service

Following replacement of the failed blower, the Clearwater E6 was recommissioned and fully tested.

  • New JDK 60 air blower installed
  • Full electrical inspection completed
  • Operational testing completed
  • Aeration restored
  • No further faults identified
  • Plant returned to normal operation

Why Routine Servicing Matters

Routine servicing helps identify worn or deteriorating components before they cause prolonged disruption to the treatment process.

Replacing a failed air blower promptly reduces the time that the biological treatment process is without oxygen and helps restore normal treatment performance as quickly as possible.

We provide Clearwater E6 servicing, air blower replacements and sewage treatment plant repairs throughout Scotland.