Caledonia Environmental

Bioficient 5 & P6 BioTec Service – Eyemouth, Scottish Borders | Caledonia Environmental

Bioficient 5 & P6 BioTec Service – Eyemouth, Scottish Borders | Caledonia Environmental Bioficient 5 & P6 BioTec Service – Eyemouth, Scottish Borders Bioficient 5 service Eyemouth and P6 BioTec service Eyemouth completed today on the same farmgrounds. Both systems had developing issues which, if left unresolved, would have led to breakdowns and non-compliance. Our […]

Bioficient 5 & P6 BioTec Service – Eyemouth, Scottish Borders | Caledonia Environmental Read More »

P6 BioTec Service – Crieff, Scotland

P6 BioTec Service – Crieff, Scotland | Caledonia Environmental P6 BioTec Service – Crieff, Scotland P6 BioTec service Crieff carried out today as part of routine maintenance. This system is fitted with a JDK-60 air blower and a green Darcy Kingspan control panel. The service included a full mechanical and electrical inspection, ensuring the BioTec

P6 BioTec Service – Crieff, Scotland Read More »

Raw sewage pump and pump chamber

Sewage Pump Chamber Service – Drymen, Stirlingshire | Caledonia Environmental

Sewage Pump Chamber Service – Drymen, Stirlingshire | Caledonia Environmental Sewage Pump Chamber Service – Drymen, Stirlingshire Sewage pump chamber service Drymen carried out as a routine visit for an existing client. The installation comprises 2 × Vortex F 50.75.1M pumps running at 230 V (both steady at 6 A under load), 4 floats (stop, start, assist, high-level)

Sewage Pump Chamber Service – Drymen, Stirlingshire | Caledonia Environmental Read More »

heq sewage plant

HEQ Sewage Treatment Plant Service – Dundee, Scotland

HEQ Sewage Treatment – Routine Service Dundee | Caledonia Environmental HEQ Sewage Treatment – Routine Service in Dundee, Scotland HEQ routine service Dundee carried out today for an existing customer. During the visit, we recorded an MLSS concentration above 70%, identified a blocked recycle pump, and found the 250 L/min airflow filter fully choked. Each

HEQ Sewage Treatment Plant Service – Dundee, Scotland Read More »

P150 BioTec Annual Service – Dunning, Perth & Kinross

P150 BioTec Annual Service – Dunning, Perth & Kinross P150 BioTec Annual Service – Dunning, Perth & Kinross P150 BioTec annual service Dunning completed as part of routine maintenance. The plant was showing signs of poor treatment due to ponding on the Enkamat filter media. Spray cones were inspected and confirmed clear. These issues were

P150 BioTec Annual Service – Dunning, Perth & Kinross Read More »

Klargester BioTec service and repair

BioTec Repair & Service Avonbridge Falkirk – Caledonia Environmental

BioTec Repair & Service Avonbridge Falkirk – Caledonia Environmental BioTec Repair & Service – Avonbridge, Falkirk BioTec repair Avonbridge carried out today after a customer reported bad smells, no spray, and no blower noise. On inspection, we found the blower had failed completely. To resolve the issue, we installed a new energy-efficient blower, reducing electricity

BioTec Repair & Service Avonbridge Falkirk – Caledonia Environmental Read More »

Drive end Bracket support

BA BioDisc Repair Kinloss Forres – Caledonia Environmental

BA BioDisc Repair Kinloss Forres – Caledonia Environmental BA BioDisc Repair – Kinloss, Forres, Moray BA BioDisc repair Kinloss completed after ongoing breakdowns over the past two years. Previous contractors had been unable to resolve repeated failures. Our inspection identified severe alignment issues, sheared rotor tubes, pulley misfit, and GRP damage requiring specialist repair. Bespoke

BA BioDisc Repair Kinloss Forres – Caledonia Environmental Read More »

BD BioDisc Repair – West Linton, Scottish Borders

BD BioDisc Repair West Linton – Caledonia Environmental BD BioDisc Repair – West Linton, Scottish Borders BD BioDisc repair West Linton for a unit identified during last month’s inspection as high risk for failure. Today we completed the major works: the drive train was rebuilt, bearings replaced using our lifting frame, and the loss-of-rotation system

BD BioDisc Repair – West Linton, Scottish Borders Read More »

BA Klargester BioDisc Service – Biggar, South Lanarkshire

BA BioDisc Service Biggar – Caledonia Environmental BA Klargester BioDisc Service – Biggar, South Lanarkshire BA BioDisc service completed in Biggar, South Lanarkshire. We carried out a full mechanical and electrical check, an internal pressure wash where appropriate, and a final function test to keep the plant running smoothly and within discharge expectations. BA BioDisc

BA Klargester BioDisc Service – Biggar, South Lanarkshire Read More »

Biodisc rotor alignment

Klargester BioDisc Repair & Overhaul – Forres, Moray

Klargester BioDisc Repair Forres – Caledonia Environmental Klargester BioDisc Repair & Overhaul – Forres, Moray Klargester BioDisc repair completed in Forres, Moray. Severe neglect had left the drive system rusted and rotation poor. We carried out a full mechanical overhaul and returned the plant to smooth, compliant operation. Forres BioDisc after overhaul: smooth rotation and

Klargester BioDisc Repair & Overhaul – Forres, Moray Read More »