BA BioDisc service Strathaven completed for a new customer after a red warning light and F8 loss of rotation alarm appeared on the control panel. The fault was traced to a failed rotation sensor, which was replaced and tested. This call-out also included a full service to restore reliable operation and confirm compliance with SEPA discharge standards.

Old and new belt during BA BioDisc service Strathaven
Old and new drive belts installed during the BioDisc service in Strathaven.

✅ Fault diagnosis and service tasks

  • Rotation sensor: Faulty loss-of-rotation sensor replaced; alarm system tested and confirmed operational.
  • Drive belt: Existing belt heavily cracked and slipping. Replaced with new OEM belt and re-tensioned correctly.
  • Control panel: Green Darcy Kingspan panel inspected; F8 fault cleared, power and alarm circuits verified.
  • Bearings and gearbox: Checked for noise, heat and vibration – all operating within specification.
  • Electrical tests: 239 V supply steady; insulation and current draw verified during rotation checks.
  • Chamber inspection: Low sludge and crust levels; tank does not require emptying at this time.

After completing these works, the BioDisc was run under observation – rotor alignment, belt tension and alarm reset all confirmed correct. The system now operates quietly and efficiently.

Cracked BA BioDisc drive belt replaced Strathaven
Heavily cracked BA BioDisc drive belt identified and replaced during service.

🧰 Electrical repairs and testing

During inspection, the junction box terminals were renewed to maintain safe and reliable electrical continuity. All alarm circuits were tested, including loss-of-rotation and power-failure functions. The plant was left in automatic mode with visual indicators proven.

Old and new rotation sensor replacement BA BioDisc Strathaven
Replacement of the faulty rotation sensor resolving the F8 loss-of-rotation fault.
Renewed junction box terminals BA BioDisc Strathaven
Renewed junction box terminals ensuring safe, watertight electrical connections.

🛠 Why prompt servicing matters

Ignoring a BioDisc fault such as a loss-of-rotation alarm can quickly lead to treatment failure, odours and costly component wear. Routine inspection and timely belt or sensor replacement prevent total breakdowns and extend system life.

📅 Service contracts available

We provide annual BioDisc service contracts across Strathaven, Lesmahagow, Larkhall and the wider South Lanarkshire area, including mechanical, electrical and structural inspections to keep your sewage treatment plant compliant and dependable.

Learn more about our sewage treatment plant servicing or visit SEPA for discharge regulation guidance.

📞 Book a BioDisc Service in Strathaven